High efficiency GHP AISIN at partial loads

GHP-Dx performances at partial load.High efficiency  GHP AISIN   increases at partial loads.

Here is an example GHP20HP unit nominal power rating of 56 kW in cooling and 63 kW  in heating.

Cooling mode, outdoor temperature +35°C

 

       Load                            % Capacity        kW Gas consumption              kW WKIT        kW GUE    %
100 56,00 40,70 20,35 188
90 50,40 35,50 17,75 192
80 44,80 30,20 15,10 198
70 39,20 25,00 12,50 207
60 33,60 20,20 10,10 216
50 28,00 16,00 8,00 225

Heating mode, outdoor temperature  +6°C.

           Load                         % Capacity      kW Gas     consumption                   kW WKIT            kW GUE %
100 63,00 42,00 10,50 175
90 56,40 36,00 9,00 182
80 50,00 31,10 7,78 186
70 43,60 26,50 6,63 190
60 37,20 22,20 5,55 193
50 30,90 18,00 4,50 197

Below data for all models without recovery heat for sanitary hot water production :

GHP-Dx performances at partial load.